You are currently viewing 50 MCQ’s on Fire Tenders IS Codes

50 MCQ’s on Fire Tenders IS Codes

  • Post author:
  • Post category:Blog

1. What is the minimum water tank capacity required for Water Tender Type A as per IS 948?
a) 1,000 liters
b) 2,000 liters
c) 3,000 liters
d) 4,000 liters
Ans. c) 3,000 liters

2. What is the maximum distance from which a water jet can be thrown by the pump of a Water Tender Type A as per IS 948?
a) 15 meters
b) 25 meters
c) 35 meters
d) 45 meters
Ans. b) 25 meters

3. What type of pump is required for a Water Tender Type A as per IS 948?
a) Positive displacement pump
b) Centrifugal pump
c) Rotary pump
d) Diaphragm pump
Ans. B) Centrifugal pump

4.What is the minimum engine power required for a Water Tender Type A as per IS 948?
a) 50 hp
b) 75 hp
c) 100 hp
d) 125 hp
Ans. C) 100 hp

5. What is the minimum clearance required for a Water Tender Type A as per IS 948?
a) 2.5 meters
b) 3 meters
c) 3.5 meters
d) 4 meters
Ans. b) 3 meters

6. What is the minimum water tank capacity required for Water Tender Type B as per IS 950?
a) 2,000 liters
b) 3,000 liters
c) 4,000 liters
d) 5,000 liters
Ans. D) 5,000 liters

7. What is the maximum distance from which a water jet can be thrown by the pump of a Water Tender Type B as per IS 950?
a) 20 meters
b) 30 meters
c) 40 meters
d) 50 meters
Ans. C) 40 meters

8. What type of pump is required for a Water Tender Type B as per IS 950?
a) Positive displacement pump
b) Centrifugal pump
c) Rotary pump
d) Diaphragm pump
Ans. B) Centrifugal pump

9. What is the minimum engine power required for a Water Tender Type B as per IS 950?
a) 75 hp
b) 100 hp
c) 125 hp
d) 150 hp
Ans. B) 100 hp

10. What is the minimum clearance required for a Water Tender Type B as per IS 950?
a) 2.5 meters
b) 3 meters
c) 3.5 meters
d) 4 meters
Ans c) 3.5 meters

11. What is the minimum water tank capacity required for Water Tender Type B as per IS 950?
a) 2,000 liters
b) 3,000 liters
c) 4,000 liters
d) 5,000 liters
Ans. D) 5,000 liters

12. What is the maximum distance from which a water jet can be thrown by the pump of a Water Tender Type B as per IS 950?
a) 20 meters
b) 30 meters
c) 40 meters
d) 50 meters
Ans. C) 40 meters

13. What type of pump is required for a Water Tender Type B as per IS 950?
a) Positive displacement pump
b) Centrifugal pump
c) Rotary pump
d) Diaphragm pump
Ans. B) Centrifugal pump

14. What is the minimum engine power required for a Water Tender Type B as per IS 950?
a) 75 hp
b) 100 hp
c) 125 hp
d) 150 hp
Ans. B) 100 hp

15. What is the minimum clearance required for a Water Tender Type B as per IS 950?
a) 2.5 meters
b) 3 meters
c) 3.5 meters
d) 4 meters
Ans c) 3.5 meters

16. What is the minimum water tank capacity required for a Crash Fire Tender as per IS 951?
a) 1,500 liters
b) 2,500 liters
c) 3,500 liters
d) 4,500 liters
Ans. b) 2,500 liters

17. What is the minimum foam tank capacity required for a Crash Fire Tender as per IS 951?
a) 100 liters
b) 200 liters
c) 300 liters
d) 400 liters
Ans. c) 300 liters

18. What type of foam is required for a Crash Fire Tender as per IS 951?
a) Protein-based foam
b) Synthetic-based foam
c) Fluoroprotein-based foam
d) Alcohol-resistant foam
Ans. d) Alcohol-resistant foam

19. What is the minimum engine power required for a Crash Fire Tender as per IS 951?
a) 250 hp
b) 300 hp
c) 350 hp
d) 400 hp
Ans. b) 300 hp

20. What is the minimum clearance required for a Crash Fire Tender as per IS 951?
a) 2.5 meters
b) 3 meters
c) 3.5 meters
d) 4 meters
Ans. C) 3.5 meters

21. What is the minimum sound pressure level required for fire alarm sounders as per IS 2189?
a) 70 dB
b) 80 dB
c) 90 dB
d) 100 dB
Ans c) 90 dB

22. What type of detectors are used for early detection of fire in high-risk areas as per IS 2189?
a) Smoke detectors
b) Heat detectors
c) Flame detectors
d) Multi-sensor detectors
Ans. d) Multi-sensor detectors

23. What is the minimum clearance required for manual call points from the floor level as per IS 2189?
a) 0.5 meters
b) 1 meter
c) 1.5 meters
d) 2 meters
Ans. b) 1 meter

24. What is the minimum operating temperature range required for fire detection and alarm system components as per IS 2189?
a) -5°C to 40°C
b) 0°C to 50°C
c) 5°C to 60°C
d) 10°C to 70°C
Ans. B) 0°C to 50°C

25. What is the minimum battery backup time required for the fire detection and alarm control panel as per IS 2189?
a) 1 hour
b) 2 hours
c) 3 hours
d) 4 hours
Ans. c) 3 hours

26. What is the minimum distance required between two fire extinguishers of same type as per IS 2190?
a) 2 meters
b) 3 meters
c) 4 meters
d) 5 meters
Ans. b) 3 meters

27. What is the minimum length of the hose provided with a water type fire extinguisher as per IS 2190?
a) 1 meter
b) 2 meters
c) 3 meters
d) 4 meters
Ans. C) 3 meters

28. What is the minimum discharge time required for a carbon dioxide type fire extinguisher as per IS 2190?
a) 6 seconds
b) 8 seconds
c) 10 seconds
d) 12 seconds
Ans. b) 8 seconds

29. What is the minimum fire rating required for a fire extinguisher used for Class A fires as per IS 2190?
a) 1A
b) 2A
c) 3A
d) 4A
Ans. b) 2A

30. What is the maximum distance from the floor level at which a fire extinguisher can be installed as per IS 2190?
a) 1 meter
b) 1.5 meters
c) 2 meters
d) 2.5 meters
Ans. C) 2 meters

31. What is the minimum length of the ladder required for an Emergency Rescue Tender as per IS 949?
a) 8 meters
b) 10 meters
c) 12 meters
d) 14 meters
Answer: b) 10 meters

32. What is the minimum capacity of the water tank required for an Emergency Rescue Tender as per IS 949?
a) 1,000 liters
b) 2,000 liters
c) 3,000 liters
d) 4,000 liters
Answer: c) 3,000 liters

33. What is the minimum clearance required for the working platform of the turntable ladder as per IS 949?
a) 2 meters
b) 2.5 meters
c) 3 meters
d) 3.5 meters
Answer: c) 3 meters

34. What is the minimum length of the rescue ladder required for an Emergency Rescue Tender as per IS 949?
a) 4 meters
b) 5 meters
c) 6 meters
d) 7 meters
Answer: b) 5 meters

35. What is the minimum length of the hydraulic rescue equipment hose required for an Emergency Rescue Tender as per IS 949?
a) 10 meters
b) 15 meters
c) 20 meters
d) 25 meters
Answer: b) 15 meters

36. What is the minimum capacity of the water tank required for a 2000 Kg DCP Tender as per IS 10993?
a) 1000 liters
b) 2000 liters
c) 3000 liters
d) 4000 liters
Answer: b) 2000 liters

37. What is the minimum diameter of the hose used for water filling in a 2000 Kg DCP Tender as per IS 10993?
a) 50 mm
b) 65 mm
c) 75 mm
d) 100 mm
Answer: b) 65 mm

38. What is the minimum distance required between the ground clearance and the lowest point of the 2000 Kg DCP Tender as per IS 10993?
a) 250 mm
b) 300 mm
c) 350 mm
d) 400 mm
Answer: b) 300 mm

39. What is the minimum discharge time required for a 2000 Kg DCP Tender as per IS 10993?
a) 30 seconds
b) 40 seconds
c) 50 seconds
d) 60 seconds
Answer: a) 30 seconds

40. What is the minimum diameter of the DCP discharge outlet required for a 2000 Kg DCP Tender as per IS 10993?
a) 19 mm
b) 25 mm
c) 32 mm
d) 38 mm
Answer: c) 32 mm

41. What is the minimum length of the ladder required for a Rescue Tender as per IS 956?
a) 6 meters
b) 8 meters
c) 10 meters
d) 12 meters
Answer: b) 8 meters

42. What is the minimum capacity of the water tank required for a Rescue Tender as per IS 956?
a) 1000 liters
b) 2000 liters
c) 3000 liters
d) 4000 liters
Answer: b) 2000 liters

43. What is the minimum clearance required for the working platform of the turntable ladder as per IS 956?
a) 2 meters
b) 2.5 meters
c) 3 meters
d) 3.5 meters
Answer: c) 3 meters

44. What is the minimum length of the rescue ladder required for a Rescue Tender as per IS 956?
a) 4 meters
b) 5 meters
c) 6 meters
d) 7 meters
Answer: b) 5 meters

45. What is the minimum length of the hydraulic rescue equipment hose required for a Rescue Tender as per IS 956?
a) 10 meters
b) 15 meters
c) 20 meters
d) 25 meters
Answer: b) 15 meters

46. According to IS 8758, what is the minimum distance required between two temporary structures or pandals?
a) 2 meters
b) 3 meters
c) 4 meters
d) 5 meters
Answer: b) 3 meters

47. What is the minimum number of fire extinguishers required for a temporary structure or pandal as per IS 8758?
a) 1
b) 2
c) 3
d) 4
Answer: b) 2

48. According to IS 8758, what is the maximum height allowed for a temporary structure or pandal?
a) 4 meters
b) 6 meters
c) 8 meters
d) 10 meters
Answer: c) 8 meters

49. What is the minimum distance required between the temporary structure or pandal and any other permanent structure as per IS 8758?
a) 1 meter
b) 2 meters
c) 3 meters
d) 4 meters
Answer: c) 3 meters

50. What is the minimum width of a staircase in a high-rise building as per NBC Part 4?
a) 800 mm
b) 900 mm
c) 1000 mm
d) 1100 mm
Answer: c) 1000 mm